MD1P

MD1P is a module for FYRA loops designed for the simple control of 1 door. It is equipped with 1 balanced input and 1 output associated between them to receive signals from devices or detectors to control 1 door or 1 fire door and to activate their closure with its output relay. The module also features 1 independent balanced / non-balanced input for alarm and fault (open line and line short circuit) used to connect on the loop 1 detector or other conventional device equipped with N.O. relay contacts.

MD1P has an on-board line isolator and three 2-colour LED indicators for inputs and output relay status. The setup of the ID address is immediate and is made via rotary switch while module functions are set using the dipswitch.
The plastic case makes the module suitable to be installed in 503 flush-mount boxes. MD1P certifications: CPR 305/2011 EN54-17 and EN54-18.

Tags

  • Doors control

    1 door simple control

    Independent inputs

    1 input

    Use

    1 balanced input and 1 output associated between them to receive signals from devices for 1 door or fire damper control and to command their closure with his output relay. Each control relay output is associated with 1 input which manage door closed status

    1 balanced / not balanced input for alarm and fault (line opening and line short circuit), used to connect on the loop 1 detector or other conventional device provided with relay outputs on the loop

    Integrated isolator

    Yes

    Addressing

    Via rotary switch

    Relay contact range

    0.5 A at 125 Vac - 2 A at DC 30 V

    Dimensions and weight

    W 91,6 x H 54,7 x D 20 mm, 58 g

    Power consumption

    1,8 mA idle status (bilance inputs), 4,7 mA when short circuit (isolator activation) 3,2 mA alarm status

    Power supply

    DC24V from loop

    Certification

    Certification CPR 305/2011 EN54-18 and EN54-17

  • Datasheet

    • Foglio tecnico
      Model
      09/07/2020
       
    • Datasheet
      Model
      09/07/2020
       

    Product Description

    • Descrizioni Capitolato
      Model
      09/07/2020
       
    • Product Description
      Model
      09/07/2020
       

    Technical Manual

    • Manuale Tecnico
      Model
      06/10/2020
       
    • Technical Manual
      Model
      06/10/2020
       

    CE - DoP

    • CE - DoP
      Model
      25/11/2020
       
    • CE - DoP
      Model
      25/11/2020
       

    Notified Body

    • Ente Notificato
      Model
      25/11/2020
       
    • Notified Body
      Model
      25/11/2020
       
  • Technical Manual

    • Manuale Tecnico
      Model
      19/06/2017
       
    • Technical Manual
      Model
      19/06/2017
       
    • MIIE0MP00700
      Modulo incendio analogico controllo porta 2 ingressi / 1 uscita + 1 ingresso aggiuntivo con isolatore FYRA
    • MIIE0MP00500
      Modulo incendio analogico IE2 controllo porta 2 ingressi / 1 uscita + 1 ingresso aggiuntivo con isolatore

Active Products