Type |
The MDCONV module lets you monitor conventional fire detectors and manual alarm call points in a compatible analogue-addressable loop |
Integrated isolator |
Yes |
Addressing |
Through dipswitch |
Dimensions |
W 150 x H 90 x D 46 mm |
Power consumption |
3.8 mA when idle (including balancing resistor, excluding detectors); 4 mA for 150 ms when turning on; 13 mA in alarm; 13 mA with short-circuited line. Note: values measured with the 6.2 kΩ balancing resistor |
Power supply |
DC24V from loop |
Certification |
Certification CPR 305/2011 EN54-18 and EN54-17 |