Type |
Manual indoor analogue-addressable call point for FYRA loop |
Integrated Isolator |
Yes |
Alarm |
Manual alarm generated by pressing the center of the front glass recoverable |
Addressing |
Via rotary switch |
Signallings |
2 yellow LEDs of isolating circuit, 1 polling green LED, 1 advertising colored bar and 1 alarm red LED |
Installation |
Indoor |
IP class |
IP2XD |
Operative conditions |
from -10°C to +50°C, -93%U.R. |
Dimensions |
W 90 x H 90 x D 60 mm |
Reset device |
Provided |
Power consumption |
500µA idle status, 4,7mA when short circuit, 1,8 mA alarm status |
Power supply |
DC24V (from 20,5 to 27,5 V) |
Certification |
Certified CPR 305/2011 EN54-11 and EN54-17 |