Number of detection loop | Up to 5 |
Number of loop address | 254 (up 512 per control unit) |
Protocols |
AS with FX/EXP01 module Evolution with FXEXPEV IE with FXEXPIE module |
Zones number | 120 |
FXUP expansion | Up to 3 FXUP additional |
Fault relay output | 2 outputs |
Alarm relay output | 1 programmable output |
Supervised alarm outputs | 3 programmable outputs + 1 not programmable output |
DC24V output (LOAD) | 1 |
General LEDs indication | Yes |
LCD display | 4 x 20 character |
Control panel | Built-in for management and programming |
Management levels | 3 access levels with 10 associated user password from step 1 at 2 level and 10 installer password associated from step 2 to level 3 |
Peripherals serial lines | 1 for repeaters, synoptic and “intelligent” power supplies units management |
Extinguishing management | Through external control unit |
Remote assistance | With WINFIRE PRO software |
Management software | With GLOBALPRO, GPROFIRE and WINFIRE PRO software |
Control units and PC network | Up to 16 |
Events storage | 4000 events |
Devices storage | Graphic display of the log devices |
Functions |
Management of input and output devices through logic events, system events, and patterns Definition of filters for special management of events memory and printing process; Weekly programmer with day/night function Date/time setup and daylight saving time switch Sensor control Delayed mode Sensitivity with thresholds that can be programmed for alarm, pre-alarm, and maintenance Loop devices self-learning with double-address identification |
Power supply units | 4A @ DC24V: 1,5A buffer battery charge, 0,5A max to the LOAD terminal for auxiliary device powered |
Allocable batteries (not included) | 2 x 26Ah/12V |
Power consumption (Absorption of any device linked to the relay outputs of panel and unit boards is not included) |
810 mA @ 230 VAC from mains. Unit boards: 280 mA @ 24 VDC at rest, 410 mA @ 24 VDC in alarm conditions (max 520 mA when the max number of contemporaneously lit LEDs is on). For each FXMASTERINT board: 12 mA @ 24 VDC. Absorption of FX/EXP01single loop boards: 31 mA @ 24 VDC (without detectors), 82 mA @ 24 VDC (with 254 detectors (using smoke detectors) Absorption of FXEXPEV single loop boards: 75 mA @ 24 VDC (without detectors), 150mA @ 24 VDC (with 254 detectors (using smoke detectors) Absorption of FXEXPIE single loop boards: 25 mA @ 24 VDC (without detectors), 165mA @ 24 VDC (with 254 detectors (using smoke detectors) |
Power supply | 230 Vca |
Operating temperature | -5 / +40°C, 93% U.R. |
Dimensions and weight | W500 x H570 x D190 mm, 15,5Kg (with transformer) |
Protection class | IP3X |
Certifications | CPR 305/2011 certification (ex CPD 89/106/EEC certification) EN54-2 and EN54-4 |