Loop |
|
Connectable devices |
- Max. 254 devices on the loop
|
Protocols |
- AS (with FX/EXP01 module)
- Evolution (with FXEXPEV module)
- IE (with FX/EXPIE module)
|
Zones |
|
Dispaly and LED |
- Programming keyboard
- LED indicators for signalling and operating status
- LCD display for visualization and programming
- LED on mainboard for power supply, F2, F3, F4 fuses fault.
|
Relays |
- RELAY 1 alarm relay and RELAY 2 with contacts in change at 8A at AC250V
|
Connection terminal on main board for |
- 1 supervised output freely programmable for BELL,
- RELAY 1 output for FAULT event with C - NA – NC contacts,
- RELAY 2 output FIRE ALARM that can be programmed to signal events with C-NO-NC contacts,
- LOAD DC24V output.
- RS-485 output on FX10485 optional board to manage peripherals as: power supply units, repeater panels and synoptic repeater
|
Connectors on main board for: |
- 1 optional loop expansion board (choose from FX/EXP01, FXEXPEV or FXEXPIE),
- 1 FX10485 serial interface board (optional),
- 1 optional ETRLAN board,
- For power cable from mains transformer secondary winding,
- For optional board to view FX/EXP10 40 zones,
- Minidin FIRMWARE connector to download firmware.
- Minidin MODEM-PC connector to connect the indicated devices,
- Minidin PRINTER connector to connect PRT serial printer
|
Functions |
- Management of inputs and output devices through logic events, system events
- Management of outputs devices through logic events, system events and pattern
- Definition of filters for management of events memory and printing process;
- Weekly Programmer with Day/Night function
- Date/time setup and daylight saving time switch;
- Detectors check
- Delay mode
- Sensitivity with thresholds that can be programmed
- by alarm, pre-alarm, and maintenance
- Self-learning of loop devices with double address identification
- Maintenance management with percent parameters of detectors, alarm type and print
|
Arrangements |
- Cable with connector to connect and manage several power units, FXC72H cable required (optional).
- Cable with NTC to fix directly on one of the batteries housing to control current supply related to internal temperature.
|
Operating temperature |
|
Dimensions and weight |
- W 325 x H 304 x D 133 mm, 5Kg
|
Protection class |
|
Power consumption |
- From network: 350mA @ AC 230 V
- Main board: 120mA @ DC 24 V
- FX/EXP01 loop board: 10 mA @ DC 24 V without detectors , 60 mA @ DC 24 V with 254 connected detectors (calculated with smoke sensors).
- FXEXPEV loop board: 75 mA @DC 24 V without detectors, 150 mA @ DC 24 V with 254 connected detectors (calculated with smoke sensors).
- FXEXPIE loop board: 25 mA @DC 24 V without detectors,165 mA @ DC 24 V with 254 connected detectors (calculated with smoke sensors).
|
Power supply |
- AC 230 V, 50Hz
- DC 24 V power supply unit included
- Batteries: 2 x 7Ah/DC 12 V mod. B712G
|
Certification |
- Certified CPR 305/2011 (e CPD 89/106/CEE certification) EN54-2 and EN 54-4
|
Parts supplied |
- Connection cable in series of the buffer batteries, technical manual, user's manual, CD with WINFIRE/STD 4.x browser.
|