FXMASTER

FXMASTER is the supervisor panel able to interface and manage up to 4 fire detection control units choosing by FX/10, FX/20 and FX/50. In addition it is possible to realize via RS485 a network (up to 8 panels) choosing by FXMASTER and FXPRO. These panels can manage a control units network composed up to 8 units choosing by FX/10, FX/20, FX/50, FXPRO and FXUP.

With the creation of a FXMASTER network is possible to manage, from any FXMASTER, all the fire detection control units connected to the other FXMASTER supervisors panels and FXPRO control units. In addition, FXMASTER allows to a single fire detection control unit to extend the alarm condition even to the entire FXMASTER network and to their control units connected.

FXMASTER can be integrated with existing systems managed by GLOBALPRO, GLOBALMANAGEMENT or GLOBALFIRE softwares and is recognised like a normal keyboard connected to the control unit. Required 1 FXMASTERINT board interface for each control unit and for each FXMASTER to connect.

  • Functions
    • Remote management of FX series unit network
    • FXMASTER emulates a reapeater for all linked FX series control units
    • Advanced function of alarms extension
    • Max 4 connectable control units (FX/10, FX/20, FX/50) on the same panel
    • Alarm or fail zones viewing from every FX control unit linked
    • EVACUATE command sending to every unit of the network at the same time
    • RESET command sending to every unit of the network at the same time
    • SILENCE command sending to every unit of the network at the same time
    • Possibility to realize, via RS485, a network (up to 8 panels) choosing by FXMASTER and FXPRO. These panels can manage a control units network composed up to 8 units choosing by FX/10, FX/20, FX/50, FXPRO and FXUP
    Compatible lines FX/10, FX/20, FX/50, FXPRO
    Connections
    • 1 Power supply input
    • 1 alarm output
    • 1 fail output
    • 5 socket for FXMASTERINT boards connection (not provided)
    FXMASTERINT connections
    • 1 connection for RS485 serial line
    • 1 connection for alarm transmission line
    Signallings
    • 24 LED for simultaneous control units monitoring
    • 14 LED for aggregate monitoring
    • 15 LED for units emulation
    • LCD display with buttons
    • Internal buzzer
    Operating temperature -5°C / +40 °C,  93% U.R.
    Protections class IP3X
    Dimensions W 204 x H 250 x D 50 mm
    Weight 1,5 Kg
    Power consumption
    • 57 mA idle status
    • 159 mA alarm status
    • 267 mA max alarm status
    • 12 mA idle status and alarm status for every FXMASTERINT board installed on panel’s sockets
    • 2 mA idle status and 6 mA alarm status for every unit linked to network
    Power supply 24 Vdc provided from control unit or from a remote power supply unit
    Certification Certification CPR 305/2011 (ex CPD 89/106/EEC certification) EN54-2 and EN54-4
    Parts supplied Technical manual, 4700 Ohm end line resistor
  • Datasheet

    • Foglio tecnico
      Model
      24/05/2016
       
    • Datasheet
      Model
      24/05/2016
       

    Product Description

    • Descrizioni Capitolato
      Model
      24/05/2016
       
    • Descrizioni Capitolato
      Model
      24/05/2016
       

    User Manual

    Technical Manual

    • Manuale Tecnico
      Model
      10/05/2016
       
    • Technical Manual
      Model
      10/05/2016
       

    CE - DoP

    • CE - DoP
      Model
      13/06/2017
       
    • CE - DoP
      Model
      13/06/2017
       

    Notified Body

    • Ente Notificato
      Model
      13/06/2017
       
    • Ente Notificato
      Model
      13/06/2017
       
    • AIACFMC00100
      Pannello controllo e supervisione centrali serie FX-FXPRO-FXUP

Active Products